Category: Liquid Cooling

  • What Is a CDU? Coolant Distribution Units Explained

    What Is a CDU? Coolant Distribution Units Explained

    Quick answer: A coolant distribution unit, or CDU, circulates and manages coolant serving liquid-cooled IT equipment. In a common liquid-to-liquid arrangement, it transfers heat between a technical cooling loop and a separate facility-water loop. Other designs reject heat to air. Select a CDU by its supported operating conditions, interfaces and maintenance requirements—not only the advertised kilowatt rating.

    Illustration of a liquid-cooled modular data center

    A cold plate removes heat from a processor, but that heat still needs a controlled route out of the rack. The CDU is a key part of that route in many liquid-cooling architectures. Understanding its role helps project teams connect server requirements to facility design and avoid gaps between otherwise compatible-looking equipment packages.

    Understand the two sides of the cooling interface

    In a typical liquid-to-liquid design, the technical cooling system carries coolant between the CDU and the IT equipment. The facility-water system carries heat away from the CDU toward the site’s heat-rejection equipment. A heat exchanger transfers energy between the circuits without normally mixing their fluids.

    This separation allows the two circuits to be managed against different requirements. The technical loop must meet the server-side specification, while the facility side must supply the conditions needed for heat exchange. Vertiv’s CDU overview describes the role of loop separation and control of temperature, pressure and flow. CDU operating principles

    The precise architecture varies by product. Ask the supplier for a system diagram that identifies the circuits, equipment boundaries and measurement points. Do not assume that a product called a CDU includes every function required by the project.

    Distinguish liquid-to-liquid from liquid-to-air

    A liquid-to-liquid CDU needs an appropriate facility cooling connection. Its performance depends on the facility-side temperature and flow as well as the technical-loop conditions. It does not independently make the incoming facility water colder.

    A liquid-to-air arrangement transfers heat from the coolant to surrounding air. This can support some deployments where a suitable facility-water connection is unavailable, but the room cooling system must still remove that heat. The heat has moved into the room rather than disappeared.

    Compare both options using the actual rack load, available services and required operating conditions. A convenient installation route is valuable only if the receiving facility can handle the resulting heat and operational requirements.

    Choose placement around capacity and access

    An in-rack CDU places the equipment within a rack footprint. An in-row or adjacent unit can serve a group of racks, depending on the system design. Larger arrangements may distribute coolant across broader parts of a facility.

    These terms describe placement, not a universal capacity range. Check the available rack space, floor area, pipe routes and service clearances for the selected product. Identify which racks are affected when the unit requires maintenance.

    A shared CDU can consolidate equipment, but it also creates a shared service boundary that must be evaluated. An in-rack arrangement can offer a more localized boundary while consuming space and requiring maintenance access at each location.

    Size against the actual operating point

    Start with the liquid-cooled heat load rather than total rack power alone. Obtain the required supply temperature, allowable temperature rise, fluid specification, flow and pressure limits from the IT supplier. Include the planned operating and maintenance cases.

    Ask the CDU supplier to confirm usable capacity under those conditions. A headline rating may assume a facility-water temperature or temperature difference that the site cannot provide. Request the relevant performance data and identify any conditions that reduce available capacity.

    Pressure and flow also matter. The circuit must overcome the resistance of the installed piping, connections and equipment while remaining within their limits. Have the complete hydraulic design checked rather than assuming that a thermal rating proves adequate circulation.

    Integrated cooling infrastructure serving a data center

    Read the specification as a system

    Specification item

    Why it matters

    What to confirm

    Thermal capacity

    Heat transfer depends on operating conditions

    Rating at the project temperatures and fluid

    Temperature approach

    Heat exchange requires a temperature difference

    Defined measurement points and design load

    Flow and pressure

    Coolant must reach the IT within its limits

    Complete circuit performance

    Monitoring and controls

    Operators need visibility and agreed responses

    Integration, alarms and control responsibilities

    Maintenance configuration

    Servicing changes available equipment

    Supported load during planned interventions

    Physical arrangement

    Equipment must be installable and serviceable

    Access, weight and component removal space

    Understand what 45°C means for CDU selection

    If the servers support warm-water operation, define the temperature at the technical-loop supply or server inlet. Then establish the facility-water condition needed across the heat exchanger. A 45°C target at one point should not be copied to every point in the system.

    The difference between the relevant facility-side and technical-side temperatures is often described as the approach temperature. Confirm the supplier’s definition and rating conditions. The available temperature difference affects the heat-transfer duty the CDU can deliver.

    EPG’s Cooling Solution offers warm-water and hybrid architectures. Use the selected server requirements and the site climate to establish whether such an arrangement fits the project; a warm-water-capable CDU does not override the IT equipment’s limits.

    Review redundancy and commissioning

    Separate internal component redundancy from redundancy of the complete cooling path. Additional pumps or power supplies can address specific failures, but shared connections, heat exchangers and facility services still need review. Define which maintenance and failure scenarios the installation must support.

    Agree cleanliness, filling, fluid-quality and acceptance requirements with the suppliers before connecting the IT. Establish who verifies each circuit and who authorizes the transition to operation. Use the equipment documentation and applicable project procedures rather than a generic flushing method.

    Commission the CDU as part of the installed system. Verify the agreed flow, temperatures, monitoring and alarm behavior, then hand over the accepted settings and maintenance instructions. OCP’s cold-plate resources can help organize the interface review alongside supplier requirements.

    Connect the rack specification to the facility

    The right CDU is the one that supports the approved IT configuration within a maintainable facility design. Explore EPG’s AIDC Solution and IDC Solution to coordinate placement, capacity and expansion with the wider deployment plan.

  • Single-Phase vs Two-Phase Direct-to-Chip Cooling

    Single-Phase vs Two-Phase Direct-to-Chip Cooling

    Quick answer: Single-phase direct-to-chip cooling keeps coolant liquid as it absorbs heat. Two-phase cooling uses controlled evaporation and condensation to transfer heat. Choose between them using the server’s validated requirements, thermal performance and operating model. Chip power alone does not establish a universal point at which a facility must switch from one approach to the other.

    Server racks and aisle infrastructure in a data center

    Liquid cooling is an established design choice for high-density computing. The practical question is which cooling circuit fits the selected hardware and the facility that will support it. Comparing single-phase and two-phase systems requires more than looking at the largest heat-load figure in a product brochure.

    Understand what changes phase

    In a single-phase system, coolant passes through cold plates attached to heat-generating components and returns warmer. Heat is transferred out of that circuit through the selected cooling infrastructure, allowing the coolant to circulate again. Water-based and glycol-based fluids are common options, subject to the equipment specification.

    In a two-phase system, some coolant evaporates while absorbing heat and later condenses, releasing that heat elsewhere in the circuit. The working fluid and operating pressure influence the boiling conditions. ZutaCore’s technical explanation describes this mechanism for its direct-to-chip system; its product-specific claims should be evaluated against the proposed configuration. Two-phase cooling explained

    Both approaches can use cold plates at the processor. Neither should be confused with immersion cooling, where electronic assemblies are placed in a fluid bath. Identify the actual architecture before comparing installation or service requirements.

    Start with the server configuration

    Ask the server supplier which cooling systems and fluids it supports for the exact equipment being purchased. Record the allowed temperatures, flow or circulation requirements, pressure limits and connection specifications. The approved configuration is a stronger starting point than a general statement about a cooling technology.

    Higher processor power makes thermal design more demanding, but heat flux, cold-plate geometry and allowable component temperature also matter. A chip’s thermal design power does not independently determine the correct phase-change strategy. Compare validated performance at the required operating conditions.

    Request evidence covering the intended workload and control behavior, not only a steady-state maximum. Identify any restrictions on startup, partial loading, equipment changes or operation outside the normal envelope. Record who approves the complete combination of server, cold plate and cooling circuit.

    Compare the operating requirements

    Consideration

    Single-phase direct-to-chip

    Two-phase direct-to-chip

    Heat transfer

    Coolant warms while remaining liquid

    Coolant evaporates and later condenses

    Key design inputs

    Temperature, flow, pressure and fluid properties

    Fluid, pressure, boiling and condensation conditions

    Hardware approval

    Validate server, cold plate and coolant combination

    Validate server, evaporator and working-fluid combination

    Operations

    Plan fluid quality checks and loop maintenance

    Plan fluid management and phase-control servicing

    Facility interface

    Confirm heat exchanger and heat-rejection requirements

    Confirm condenser and heat-rejection requirements

    Integrated cooling infrastructure serving a data center

    Evaluate 45°C operation at the correct interface

    Warm-water cooling can be attractive when the IT hardware supports it. EPG’s Cooling Solution describes secondary inlet temperatures around 45°C in suitable configurations. That is a design option to validate, rather than a temperature to apply to every server or cooling technology.

    Specify whether a quoted value refers to facility water, the technical cooling loop or the server inlet. A heat exchanger needs a temperature difference to transfer heat, so temperatures at these locations are not interchangeable. For two-phase equipment, also establish which temperature and pressure describe the working-fluid circuit.

    Ask each supplier to explain the consequences for the external heat-rejection system across the site’s weather conditions. A higher supported coolant temperature may broaden the available options, but the complete design determines whether supplemental cooling is required.

    Review serviceability before comparing cost

    Single-phase maintenance planning should address fluid condition, filtration where specified, connection integrity and safe component isolation. Two-phase planning should address the selected fluid’s handling requirements and the equipment needed to service its circuit. Procedures should come from the system supplier rather than be transferred from another technology.

    For either approach, ask how technicians identify a problem, isolate the affected equipment and restore service. Review training, spare parts, fluid availability and the warranty boundaries between the cooling and server suppliers. Include practical access to the equipment in the comparison.

    The Open Compute Project publishes cold-plate resources covering interfaces, coolants and the wider technology cooling system. These can help structure a specification review, while the selected manufacturers remain responsible for approving their equipment combination. OCP cold-plate resources

    Compare proposals with the same test conditions

    Give bidders a common brief: rack configuration, thermal load, site conditions, maintenance requirements and expansion plan. Ask for performance evidence under those conditions and a list of assumptions that still need confirmation. Separate demonstrated capability from future product plans.

    Consider a project where the initial racks are already approved for single-phase cooling. A proposed move to two-phase should identify the benefit, required hardware changes and effect on support arrangements. Conversely, a validated two-phase platform should be assessed on its own requirements rather than forced into an existing water-loop specification.

    Evaluate energy and operating cost across the full heat-removal path. Include circulation equipment, heat rejection, maintenance and any remaining air-cooling load. A component-level advantage is useful only if it improves the project’s overall outcome.

    Choose a supported system, not a headline rating

    The stronger choice is the one that meets the thermal requirement with clear compatibility, maintainable equipment and a credible support plan. Agree factory and site acceptance criteria before committing to the selected system.

    Explore EPG’s AIDC Solution and Cooling Solution to coordinate rack requirements with facility cooling and modular deployment. Begin with the approved hardware specification, then evaluate the cooling architecture against the site and operational brief.

  • Data Center Liquid Cooling Comparison

    Data Center Liquid Cooling Comparison

    Quick answer: Direct-to-chip cooling pipes liquid through cold plates mounted on the chip; immersion cooling submerges whole servers in a non-conductive fluid; rear-door heat exchangers cool exhaust air at the back of the rack. Direct-to-chip is widely used for high-density AI, immersion requires fluid-compatible equipment, and rear-door cooling can retain existing air-cooled servers. The best choice depends on validated equipment requirements and the complete system design.

    Illustration of a liquid-cooled modular data center

    Once a data center accepts that air cooling can't keep up with AI workloads the next question is which liquid cooling method to use. There isn't a single right answer. The three mainstream approaches each suit different densities, budgets, and facilities. This guide compares direct-to-chip vs immersion cooling, alongside rear-door heat exchangers, so you can see where each one fits.

    The three main liquid cooling types

    All liquid cooling shares one principle: liquid carries heat away far more efficiently than air. Where the liquid cooling types differ is in how close the liquid gets to the chip, and how much of the server it cools.

    Direct-to-chip (cold plate) cooling

    Direct-to-chip cooling — also called cold plate cooling — runs coolant through metal plates pressed directly onto the hottest components, typically CPUs and GPUs. The plate absorbs heat at the source and carries it away in a closed loop to a coolant distribution unit (CDU), which rejects it to the facility's water system.

    It is the most widely adopted liquid cooling method today, and for good reason. It targets the components that produce the most heat, integrates into broadly familiar rack designs, and can often be deployed alongside existing air cooling for the lower-power parts of a server. That makes it comparatively straightforward to adopt and to retrofit into existing halls.

    The trade-off is that direct-to-chip doesn't cool everything — memory, drives, and other components may still need some airflow — so it is frequently run as part of a hybrid air-plus-liquid design.

    Immersion cooling

    Immersion cooling takes a more total approach: entire servers are submerged in a tank of non-conductive dielectric fluid that absorbs heat from every component at once. With no air gaps and no need for server fans, it captures heat extremely effectively and supports very high compute densities when the complete system is designed for them.

    Immersion comes in two forms. Single-phase immersion keeps the fluid liquid throughout, circulating it to a heat exchanger. Two-phase immersion uses a fluid that boils on contact with hot components and condenses back into liquid — a cycle that handles enormous heat loads but adds complexity and cost.

    The strengths are clear: outstanding heat capture, very high density, near-silent operation, and excellent efficiency. The trade-offs are equally real: tanks require purpose-built infrastructure, servicing hardware means dealing with fluid, and fluid and facility costs can be high. Immersion tends to make most sense for the densest, most specialised deployments rather than as a general-purpose default.

    Integrated cooling infrastructure serving a data center

    Rear-door heat exchangers

    A rear door heat exchanger replaces the back door of a rack with a liquid-cooled radiator. Hot air from the servers passes through it on the way out, transferring heat to the liquid before air re-enters the room. The servers themselves are unchanged — the cooling is applied at the rack boundary rather than at the chip.

    This makes rear-door cooling the gentlest entry point into liquid cooling. It needs no changes to the servers, works with existing equipment, and meaningfully raises the density a rack can support. Its capacity depends on airflow, water temperature and the heat exchanger rating. Check those limits against the intended rack load before choosing it for an AI deployment.

    Comparison at a glance

    Factor

    Direct-to-chip (cold plate)

    Immersion

    Rear-door heat exchanger

    How it cools

    Liquid plates on CPUs/GPUs

    Servers submerged in fluid

    Liquid radiator on rack door

    Density supported

    High

    Very high; system-dependent

    Moderate to high

    Retrofit ease

    Moderate

    Hard (new infrastructure)

    Easiest

    Server changes

    Some (plates, manifolds)

    Significant (fluid-compatible)

    None

    Maintenance

    Familiar, with liquid loop

    Handling fluid required

    Familiar

    Best fit

    Mainstream high-density AI

    Densest, specialised builds

    First step into liquid

    Which liquid cooling method is right for you?

    For compatible cold-plate systems, a warmer supply temperature around 45°C can reduce reliance on mechanical refrigeration when the climate and heat-rejection design permit it. Confirm whether the temperature refers to facility water or the server-side loop: the CDU heat exchanger introduces a temperature difference. Hardware limits, coolant chemistry, flow and pressure requirements must govern the final operating setpoint.

    The choice usually comes down to three questions: how dense are your racks, how much can you change the facility, and how far do you want to go right now? Rear-door cooling is the easiest way to start and suits moderately dense racks with minimal disruption. Direct-to-chip is the pragmatic mainstream choice for most high-density AI deployments, balancing strong performance with manageable adoption. Immersion is an option when workload, hardware compatibility and efficiency requirements justify purpose-built infrastructure.

    In practice, many facilities adopt more than one — for example, rear-door or direct-to-chip across most of the hall, with immersion reserved for the densest racks.

    Matching method to workload

    There is no universally "best" liquid cooling method — only the right fit for a given density, facility, and timeline. Direct-to-chip leads on versatility, immersion on raw capability, and rear-door on simplicity. Getting the choice right early shapes cost, efficiency, and how easily you can scale.

    To go further, explore EPG's Cooling Solution for a liquid-first approach to AI heat, or explore EPG’s AIDC Solution for integrated power and cooling planning.